Trunking Cable Trunking: Selection, Sizing and Installation Guide

Trunking cable trunking is an enclosed or semi-enclosed channel system that carries electrical and data cables on walls, ceilings or floors in a protected, organised and accessible way. It is usually made of PVC or metal and used together with covers, couplers and corner elements. Correct selection requires consideration of the IP rating, fire behaviour and cable fill ratio.

Trunking cable trunking is an enclosed profile system with a cover that carries electrical and data cables on wall, ceiling or floor surfaces in an organised, protected and accessible way. Made up of a body, cover and connection accessories, this structure protects cables from mechanical impact, dust and moisture and makes maintenance easier. For the right selection, material, IP protection class and fill ratio should be evaluated together.

This guide covers the working principle of cable trunking systems, differences in material and type, the sizing method and installation rules. Standards such as EN 61537 for cable management systems and IEC 61439-6 for enclosed busbar systems are used as the basis for the criteria.

This content is prepared especially for readers looking for answers to the following questions:

  • Engineers who want to choose the right cable trunking type at the design stage
  • Installers carrying out wiring in offices, industrial plants or data centres
  • Project managers who want to document material and size decisions with technical justification

What is trunking cable trunking and how does it work?

This trunking system is an enclosed cable management system with a covered structure that protects electrical and data cables from mechanical impact, dust and moisture. Cables are separated and routed inside the trunking, which reduces the risk of accidental contact. It is often chosen in areas with dense cabling requirements such as offices, factories and data centres.

The performance of the system depends on choosing the mechanical and electrical dimensions together. Width and height determine the cable fill ratio the trunking can accommodate. On the electrical side, the number of cables in the trunking and the resulting temperature rise must be taken into account.

Structural components

A trunking run consists of several main parts that complement each other:

  • Base: The main body where the cables are laid, which defines the system by its dimensions.
  • Cover: Protects the cable from external influences and unauthorised access, fixed with clips or screws.
  • Connection parts: Straight, internal and external corner, tee and reducer elements are used to change the direction of the run.
  • Divider: Separates power and signal cables from each other, reducing electromagnetic interference.

As a material, sheet steel is preferred with hot-dip galvanised surface (EN ISO 1461), painted finish, or PVC.

Advantages of use

The enclosed structure provides significant benefits in terms of both operation and maintenance:

  • Cables are protected against dust, moisture and impact; the appropriate IP class is selected according to the environmental conditions.
  • Extending the run and replacing cables are carried out quickly by opening the cover.
  • A tidy and aesthetic appearance is achieved.

The difference from an open cable tray is that the top of the cables is closed. When selecting products, compliance with the cable trunking systems standard EN 50085 should be sought. You can explore the cable trunking category for product variants.

Trunking cable trunking types and material selection

In a covered cable trunking system, material selection requires a combined assessment of mechanical strength, fire behaviour and corrosion resistance. The body material directly determines the environment and cable density in which the trunking will be used. Three main body types are compared below.

PVC trunking

PVC-bodied trunking is lightweight, easy to cut and corrosion resistant. It is widely preferred in dry indoor installations, office and residential applications. For products conforming to the EN 50085 series, a flame-retardant and low-smoke (halogen-free) formulation should be requested. For fire performance, the glow-wire test under IEC 60695 should be used as a reference.

Metal trunking

Steel or aluminium-bodied trunking provides high mechanical impact resistance and electromagnetic shielding. It is preferred in industrial plants and areas with a high risk of impact. For steel bodies in outdoor or humid areas, hot-dip galvanising compliant with EN ISO 1461 should be used for protection.

Property PVC Aluminium Steel (galvanised)
Weight Light Light-medium Heavy
Mechanical strength Low-medium Medium-high High
Corrosion resistance High High Depends on galvanising thickness
Typical use Dry indoor areas Light industrial Industrial, outdoor

When choosing based on environmental conditions, the following points should be considered:

  • PVC for dry indoor areas and light loads
  • Steel where there is a risk of impact and dense cable bundles
  • Galvanised steel in humid, chemically aggressive or outdoor environments
  • Halogen-free grade in enclosed public and building areas

For cover types and size options, you can explore our cable trunking product group.

How is trunking cable trunking sized?

Sizing starts with correctly calculating the ratio of the total cross-sectional area of the cables to be placed inside the trunking to the internal cross-sectional area of the trunking. This ratio is called the fill ratio and is decisive for cable heating and ease of installation. For the calculation, knowing the cable trunking internal dimensions and the outer diameters of the cables is sufficient.

Fill ratio calculation

The fill ratio is found with the following relationship: fill (%) = Σ(cable cross-sections) ÷ trunking internal cross-sectional area × 100. The cross-section of each cable is calculated from its outer diameter using the formula π·d²/4. For power cables, it is preferable that the fill ratio does not exceed 50% in general practice; the exact limit should be confirmed with the relevant specification and manufacturer data.

Two corrections are applied after the calculation. The first is the grouping factor: as the number of circuits running side by side in the same trunking increases, the current-carrying capacity of the cables decreases (IEC 60364-5-52). The second is the thermal derating factor: in enclosed trunking systems and at high ambient temperatures, cables carry less load. The nominal current value must be multiplied by these coefficients to reduce it to the actual capacity.

  1. List the outer diameters and quantities of the cables.
  2. Calculate the total cross-sectional area.
  3. Find the fill ratio and compare it with the limit value.
  4. Apply the grouping and thermal derating factors.

It is recommended to leave an additional 20% to 30% of area above the current fill for future expansion. In this way, the trunking does not need to be replaced for lines added later. You can browse our product range for size options.

Which criteria should be compared when selecting trunking cable trunking?

Trunking selection starts with the environmental conditions of the facility and the cable load. The following headings should be compared with each other at the quotation stage. The table summarises the key criteria and practical selection notes.

Criterion Technical equivalent Selection note
IP class EN 60529 degree of protection At least IP44 should be targeted in dusty or humid environments
Material PVC, steel sheet, galvanised steel Should be determined by corrosion and mechanical load
Fire class EN 13501-1 reaction-to-fire class, halogen-free options Takes priority in enclosed areas and escape routes
Earthing Continuity in metal body, EN 61537 connection requirements Contact at joints should be checked
Application area Industrial, commercial or outdoor Load and support spacing are decisive

Corrosion risk should be kept at the forefront when selecting materials. In outdoor areas or where chemical vapours are present, hot-dip galvanised steel with coating thickness verified by EN ISO 1461 is preferred. PVC trunking, on the other hand, is a light and economical alternative for dry indoor areas.

Earthing continuity is a critical criterion for metal trunking. Conductive connections must be ensured at joints, and connection points should be measured and documented after installation.

Quick selection notes by project type:

  • Dense power cable runs: heavy-duty, covered trunking
  • Control and signal lines: trunking with separating barrier to separate power and data
  • Offices and commercial buildings: PVC or seamless trunking, aesthetic installation
  • Outdoor and humid areas: galvanised steel and an appropriate IP rating

Before completing the selection, trunking capacity, fill ratio and future expansion allowance should be evaluated together. For product families, you can explore the cable trunking category.

Points to consider when installing trunking cable trunking

Installation directly determines the load-carrying capacity and service life of the cable trunking system. An incorrect route or insufficient support may cause the system to deform under its own weight. For this reason, detailed planning should be carried out before installation.

When defining the route, strong current and weak current lines must be positioned so that they are separated from each other. Support spacing should be selected according to the trunking manufacturer's load table; in practice, a spacing of 1.5 to 2 metres is generally used. The weight of the trunking, the cable load and possible vibrations must be taken into account.

Installation steps

  1. Mark the route and support points by snapping lines.
  2. Fix hangers or brackets using galvanised components compliant with EN ISO 1461.
  3. Place the trunking body straight and level, and secure the joints.
  4. Complete the installation by selecting corner, tee and reducer parts suitable for the trunking type.
  5. Before pulling cables, check that the edge surfaces are smooth.
  6. Fit the covers as the final step; take care not to leave covers open during cable pulling. You can view our cover types page for cover options.

Common mistakes

  • Extending the support spacing, causing the trunking to sag at mid-span.
  • Omitting corner and joint parts, which leads to cable sheath damage at sharp edges.
  • Friction against the trunking edge during cable pulling, damaging cable insulation.
  • Exceeding the limits set out in EN 61537 for fill ratio.
  • Unnecessary cable joints inside the trunking and insufficient ventilation.

When these checks are carried out, the cable trunking operates safely and in an orderly manner throughout its planned service life. Ensuring that every component of the system is compatible with the others during installation also noticeably reduces maintenance costs.

Conclusion: Secure your cable infrastructure with the right trunking selection

In this guide, we have seen that IP class, fill ratio and material decisions are interlinked when selecting Trunking Cable Trunking. Trunking size directly affects cable heating behaviour and ease of maintenance. For this reason, selection should not be based on a single criterion.

In summary, you can use the following points as a checklist for your application:

  • Determine the IP class suitable for the environmental conditions.
  • Keep the fill ratio within manufacturer and standard limits.
  • Select the material (PVC or galvanised steel) according to chemical and mechanical load.
  • Verify EN 61537 and, where required, IEC 61439-6 compliance in product declarations.

Key takeaways:

Criterion Recommended approach
IP class Selection based on moisture, dust and impact risk
Material PVC for indoor use, galvanised steel for outdoor and corrosive environments
Fill ratio Calculated with allowance left for heating and cable replacement
Standard EN 61537 and relevant IEC compliance

For your project's trunking size, material and product range, you can get support from the Kabelon technical team and request a quotation for this trunking system. Sharing your current cable load is sufficient to jointly determine the right solution.

Frequently Asked Questions

What is trunking cable trunking?

Trunking cable trunking is a covered cable management system that protects electrical and data cables on wall or ceiling surfaces. It organises cable routing and makes later access easier.

What should the fill ratio be in trunking cable trunking?

In general practice, no more than about 40% to 50% of the trunking's cross-sectional area should be exceeded. The exact value should be determined according to cable type, heat dissipation and the relevant standards.

What is the difference between PVC and metal trunking?

PVC trunking is a lightweight, corrosion-resistant and easy-to-install solution. Metal trunking offers better resistance to mechanical impact and fire requirements, and it can be connected to earthing.

What IP class should trunking cable trunking have?

IP20 may be sufficient in dry indoor areas, while IP44 or higher is preferred in humid, dusty or washdown areas. Selection should be made according to environmental conditions.

How is trunking installed?

First the route is marked, the base profile is fixed to the wall, and the cover is closed after the cables are placed. A continuous run is formed using corner and joint parts.

Is trunking cable trunking fire resistant?

Fire behaviour depends on the material class; halogen-free and flame-retardant products should be preferred. Product test reports should be checked against project requirements.